Mecer ME-2000-FTU/WTU Online UPS - Black

Mecer ME-2000-FTU/WTU Online UPS - Black
Mecer ME-2000-FTU/WTU Online UPS - Black
Brand: Mecer
Product Code: Mecer ME-2000-FTU/WTU
Availability: In Stock


For Bulk Orders, Please register as a wholesaler and corporate customer.
Price:
KSH77,830.0
- +
 
   - OR -   

MECER 2000VA(1600W) Smart UPS (with AVR,Monitoring Software + Cable & Built-in Surge Protection) -Serial and USB standard 4 x12V 9Ah batteries

Key Features:

  • 2KVA online UPS
  • True double-conversion
  • Wide input voltage range (110-300VAC)
  • Input power factor correction 0.98
  • Generator compatible
  • RS-232 communication port or mini slot for USB / RS-232 / AS400 /
  • SNMP communication
  • Smart battery charger design for optimized battery performance

Specifications for the product series

Product Code

ME-2000-FTUspacer

MODEL

ME-2000-FTU

CAPACITY

2000 VA / 1600 W

Voltage Range

Low Line Transfer

160VAC /140VAC/120VAC/110VAC ± 5 % or 80VAC/70VAC/60VAC/50 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)

Low Line Comeback

168VAC /148VAC/128VAC/118VAC ± 5 % or 84VAC/74VAC/64VAC/54 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)

Low Line Comeback (Auto restart)

168VAC ± 5 % or 84 VAC ± 5 % (80%~100% Load)

148VAC ± 5 % or 74 VAC ± 5 % ( 0%~ 80% Load)

High Line Transfer

300 VAC ± 5 % or 150 VAC ± 5 %

High Line Comeback

290 VAC ± 5 % or 145 VAC ± 5 %

Frequency Range

40 ~ 70 Hz (Auto sensing)

Phase

Single phase with ground

Power Factor (nominal output @ full load)

≧0.98

OUTPUT

Output Voltage

208/220/230/240 VAC or 110/115/120/127 VAC

AC Voltage Regulation (Batt. Mode)

± 1%

Frequency Range (Synchronized Range)

47 ~ 53 Hz or 57 ~ 63Hz

Frequency Range (Batt. Mode)

50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz

Current Crest Ratio

3:1

Harmonic Distortion

≦4 % THD (Linear Load)

≦7 % THD (Non-linear Load)

Transfer Time

AC Mode to Batt. Mode

Zero

Inverter to Bypass

4 ms (Typical)

Waveform (Batt. Mode)

Pure Sinewave

EFFICIENCY(Peak)

AC Mode (@ 100% RCD load)

89.3%

Battery Mode (@ 100% RCD load)

88.2%

BATTERY

Battery Type

12V / 9Ah

Battery Numbers

4

Charging Current (max.)

1.0 A

Charging Voltage

54.7 VDC ± 1%

INDICATORS

LCD Panel

UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

ALARM

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuously sounding

Dimension, D X W X H (mm)

397 x 145 x 220

Net Weight (kgs)

17.8

ENVIRONMENT

Operation Humidity

20-90 % RH @ 0- 40°C (non-condensing)

Noise Level

Less than 45dB @ 1 Meter

MANAGEMENT

Communication

USB Card / Optional RS-232 Card, SNMP Card, or AS-400 Card available

Supports Windows 2000/2003/XP/Vista/2008, Windows 7, Linux, Unix, and MAC

Optional SNMP

Power management from SNMP manager and web browser

 

Write a review